System Configuration | 1P416S | Thermal Management | Liquid Cooling | |
Number of Packs | 8pcs | Fire Protection System | Pack-level fire protection (perfluorohexane) + independent detection and protection for electrical compartments | |
Rated Voltage | 1331.2V | Auxiliary Power Supply | 220VAC/50Hz | |
Voltage Range | 1164.8~1497.6V | Communication Interface | CAN/RS485/Ethernet | |
Rated Energy | 400kWh | Communication Protocol | Modbus/IEC 61850 | |
Rated Charge/Discharge Power | 0.5P | Protection Level | IP55 | |
DC-side Efficiency | ≥93% | Corrosion Protection Level | C4 | |
Operating Temperature Range | -30℃~55℃ | Dimensions (Width * Depth * Height) | 1300*1300*2386mm | |
Storage Temperature Range | -30℃~55℃ | Weight | Approximately 3.7T | |
Operating Humidity | 5% ≤ RH ≤ 90% (non-condensing) | Certification Standards | GB/T36276,UL1973,UL9540A,IEC62619,IEC62477-1,UN38.3 | |
Operating Altitude | ≤2500m |