System Configuration | 1P416S*10 | Thermal Management | Liquid cooling | |
Rated Voltage | 1331.2V | Fire Protection System | Pack-level fire suppression (perfluorohexane) + water-based fire suppression | |
Voltage Range | 1164.8~1497.6V | Communication Interface | CAN/RS485/Ethernet | |
Rated Capacity | 4MWh | Communication Protocol | Modbus/IEC 61850 | |
Rated Charge/Discharge Power | 0.5P | Protection Level | IP55 | |
DC-side Efficiency | ≥93% | Corrosion Protection Level | C4 | |
Operating Temperature | -30℃~55℃ | Dimensions (W*D*H) | 6058*2438*2896mm | |
Storage Temperature | -30℃~55℃ | Cycle Life | 8000 cycles @ 25℃,0.5P,70% EOL | |
Operating Humidity | 5%≤RH≤90% (non-condensing) | Weight | Approximately 36.5T | |
Altitude | ≤2500m | Certification Standards | GB/T36276,UL1973,UL9540A,IEC62619,IEC62477-1,UN38.3 |